Fort Pierce, St. Lucie County
Ceiling discolouration in a beachside condo — the air handler was the source
- Property
- Beachside condominium, Hutchinson Island
- Why they called
- Recurring dark discolouration on bedroom ceilings and around supply registers
- What the inspection found
- Indoor relative humidity at 63% — above the 55% ceiling where growth stops being sustainable. Very poor duct cleanliness, a small plenum air leak, water damage with an active leak at the air handler, and visible microbial growth on HVAC-related surfaces. Black discolouration, ghosting, and darkened registers appeared in the bedroom and elsewhere in the unit, indicating a building-system problem rather than one isolated patch.
- Moisture source
- HVAC. An actively leaking, improperly installed air handler combined with sustained high humidity and condensation on cooled surfaces — not roof or plumbing intrusion.
- Recommendation
- Physical remediation of the affected materials rather than encapsulation or paint-over, replacement of visibly affected materials so secondary moisture pathways were not left in place, and evaluation of the air handler installation by a licensed HVAC contractor. Humidity control was the precondition for any of it holding.
Laboratory sampling performed